I have an UPS with two 12v 7ah lead batteries. If I want to change the batteries I would typically go with lead batteries but here’s my question, can I use some portable mobile batteries to use it?

Because I have a 20000mah inui battery that is rated for 12v at 1.5A is this a good practice to buy several of these (since they are about 20 bucks) disassemble them and use them as ups batteries?

  • ChaoticNeutralCzech@feddit.org
    link
    fedilink
    English
    arrow-up
    3
    ·
    3 hours ago

    You need a balancing BMS anyway and the UPS will not be able to charge it to what it thinks is 100% (about 15 V at trickle current) unless you trick it with a resistor (which wastes power of course).

    • MangoPenguin
      link
      fedilink
      English
      arrow-up
      2
      ·
      3 hours ago

      Yeah you need a UPS that’s OK with the BMS charge FETs opening when the battery is full.

        • MangoPenguin
          link
          fedilink
          English
          arrow-up
          2
          ·
          2 hours ago

          Some are ok with it, on a thread I saw on reddit awhile ago about LiFePo4, people had reported a few models that worked fine with the upgrade.